Microbiological assessment of indoor air quality at different sites of a tertiary hospital in South-South Nigeria


Department of Preventive and Social Medicine, Faculty of Clinical Sciences, College of Health Sciences, University of Port Harcourt, Port Harcourt, Rivers State, Nigeria

Date of Submission02-Jan-2016
Date of Acceptance27-Jun-2016
Date of Web Publication30-Aug-2016

Correspondence Address:
Best Ordinioha
P. O. Box 162 Omoku, Onelga, Rivers State
Nigeria
Login to access the Email id

Source of Support: None, Conflict of Interest: None


DOI: 10.4103/0795-3038.189459

Rights and Permissions
  Abstract 

Background: The risk of nosocomial infection is increasing due to the increasing number of patients with immune depression. Good ventilation is one of the methods used to reduce the ambient air levels of the causative agents, but this is rarely observed in Nigeria as hospital designs used to shut out the inclement weather in temperate countries are copied without many modifications, and without adequate provisions to constantly power the mechanical ventilation mechanisms. This study tested the microbiological air quality at different areas of the University of Port Harcourt Teaching Hospital to ascertain the levels of airborne bacteria and fungi in the ambient air.
Methods: The study was carried out in July 2015 in randomly selected inpatient wards, outpatient clinics, and clinical laboratories of the hospital. The assessment was carried out by exposing Petri dishes containing the appropriate culture media for about 30 min at a convenient place in each of the nine study sites. Thereafter, the plates were covered and immediately transferred to the laboratory for incubation at 37°C, for 24-48 h, for bacteria; and at room temperature, for 5-7 days, for fungi. The number and types of bacteria and fungi in the cultures were determined at the end of the incubation period.
Results: There were detectable bacteria and fungi in the ambient air of all the study sites. The mean bacterial count ranged from 9.5 colony forming unit per cubic meter (CFU/m 3 ) in the urology ward to 199.33 in the HIV clinic, with a mean of 80.0 CFU/m 3 , while the mean fungal count ranged from 10.5 CFU/m 3 in the surgery outpatient clinic (SOC) to 23.5 in the Anatomical Pathology Laboratory (APL), with a mean of 16.9 CFU/m 3 . Staphylococcus and Streptococcus were the most common bacteria in the SOC; Klebsiella was predominant in the immunization clinic; Escherichia coli were the most common in the APL, while bacillus was most frequently isolated in the gynecology ward. The fungi cultured from the study sites include Aspergillus, Penicillium, Fusarium, Trichophyton, Candida, and Rhizopus. Unlike the bacteria count, the fungal count increased in all the study sites at the end of the working day.
Conclusion: The number and types of bacteria and fungi cultured from the study sites have the potential to cause ill health. Corrective actions are therefore needed.

Keywords: Airborne bacteria, airborne fungi, indoor air quality, Nigeria, Port Harcourt


How to cite this article:
Emuren K, Ordinioha B. Microbiological assessment of indoor air quality at different sites of a tertiary hospital in South-South Nigeria. Port Harcourt Med J 2016;10:79-84

How to cite this URL:
Emuren K, Ordinioha B. Microbiological assessment of indoor air quality at different sites of a tertiary hospital in South-South Nigeria. Port Harcourt Med J [serial online] 2016 [cited 2023 Oct 2];10:79-84. Available from: https://www.phmj.org/text.asp?2016/10/2/79/189459


  Introduction Top


Although the prevalence of noncommunicable diseases has been on the increase in Nigeria in recent years, communicable diseases are still the most prevalent diseases in Nigeria. [1] Nigerian patients with communicable diseases prefer Western medicine for the treatment of their conditions because of the high cure rate achieved with the diseases, [2] but while in the hospital, the patients aggregate the various causative agents of their diseases in one place, placing other patients, visitors to the hospital, and health-care workers at risk. The risk of infection in a hospital is further increased by the increasing number of patients with immune depression as a result of HIV/AIDS and other immune-suppressing diseases such as cancer and diabetes. [3]

Hospitals are increasingly becoming epicenters of outbreaks of certain communicable diseases, including tuberculosis, [4] diarrheal diseases, [5] and viral hemorrhagic diseases. [6] It is estimated that 5-30% of patients a year develop one or more infections during a stay in hospital, costing as much as one billion Pounds a year to treat in England alone. [7] This public health problem is further exacerbated by the growing incidence of diseases such as AIDS that result in greater hospitalization and susceptibility, and the increasing resistance of the hospital-acquired infections to common antibiotics. [8]

Several of the hospitals acquired infections are airborne, and good ventilation is recognized as one of the most effective ways of reducing the risk of transmission of airborne infections in hospitals. [9] Ventilation rates lower than 2 air changes per hour (ACH) have been associated with higher tuberculin skin test conversion rates among health workers; [10] hence, the WHOs recommendation of a minimum of 80 L/s/patient (hourly average ventilation rate) for airborne precaution rooms such as theatres, and a minimum of 60 L/s/patient for general wards and outpatient departments to reduce the risk of airborne infections in the hospital. [11]

The required ventilation is not often achieved in Nigerian hospitals because of the growing practice of adopting hospital designs used to shut out the inclement weather in temperate countries without many modifications, and without adequate provisions to constantly power the mechanical ventilation mechanisms required to achieve the required number of ACH. [12] We therefore suspect that the wards, clinics, and laboratories of these hospitals are poorly ventilated and are therefore putting the health of patients, hospital visitors, and health-care workers at risk. To test this hypothesis, we assessed the microbiological air quality of the laboratories, wards, and clinics of a tertiary hospital in Port Harcourt, before and after the peak working period. We hope that the results of the study would draw attention to the hazards posed by poor ventilation, enough to elicit corrective actions. This is especially as previous Nigerian studies had failed to make this vital connection. [13],[14]


  Materials and Methods Top


The study was carried out at the University of Port Harcourt Teaching Hospital, one of the two multispecialty tertiary health-care institutions in Port Harcourt, the capital of Rivers State, South-South Nigeria. Although located in Port Harcourt, the catchment area of the hospital extends beyond Rivers State to include much of the Niger delta region; a catchment population that can be conservatively put at 10 million people. The hospital is an 800-bed multispecialist teaching hospital located in a large expanse of land, but housed in interconnected multistorey buildings that occupy a small percentage of the total land space and ventilated by both natural and mechanical ventilation. The hospital offers not only tertiary health care services but also secondary and primary health care, encouraged by the near collapse of the other facilities in the state and region. It is heavily patronized with average bed occupancy of more than 78%, and a daily average outpatient attendance of 624. It carries out an average of 8.42 surgical operations every day and handles an average of 9.24 deliveries each day.

A descriptive, cross-sectional study design was used. The microbiological air quality of randomly selected inpatient wards, outpatient clinics, and clinical laboratories of the hospital was assessed using the appropriate measuring equipment. The hospital has 23 inpatient wards, 17 outpatient clinics, and 4 clinical laboratories; out of these, only those that attend to a minimum of thirty patients in each service day were considered for the study. Subsequently, four outpatient clinics (immunization clinic, HIV clinic, surgery outpatient clinic, and antenatal clinic), three inpatient wards (gynecological ward, male surgical ward, and urology ward), and two laboratories (medical microbiology and anatomical pathology) were randomly selected for the study.

The study was carried out in July 2015 the peak of the rainy season in the study area. The assessment was carried out by exposing Petri dishes containing the appropriate culture media at a convenient place in each of the nine study sites, and at approximately one meter above the floor to simulate the breathing zone. Nutrient agar plates were used for the bacteria, while Sabouraud dextrose agar plates were used for the fungi. The Petri dishes were exposed for about 30 min to allow time for the microorganisms in the ambient air to settle into the plates. Thereafter, the plates were covered and immediately transferred to the laboratory of the department of microbiology of the University of Port Harcourt for incubation. The plates for the assessment of bacteria were incubated at 37°C for 24-48 h, while the plates for the assessment of fungi were incubated at room temperature for 5-7 days.

The microbiological assessments were carried out twice a day, between 9 and 11 am, at the peak of clinical activities, and later in the day, between 4 and 6 pm, at the end of the peak working period, in each of the study sites.

At the end of the incubation period, the number and types of bacteria and fungi in the cultures were determined as carried out in similar other studies. [13],[14],[15] The bacteria were identified based on their morphology, Gram-staining, endospore formation, and catalyze activity; and counted based on the colony forming units (CFUs) per cubic meter (CFU/m 3 ). The number of fungi were similarly counted, while the morphology and characteristics of each of the colonies were as described by Barnet and Hunter [16] and used in other studies. [13],[14]

The data collected during the study were put in a database, and then analyzed using IBM's SPSS statistical package, Version 20 and Microsoft's Excel 2016 after checking for consistency and completeness. Summary measures were calculated for each outcome of interest, while the test of significance was conducted using the relevant statistical test at 95% confidence interval, with P ≤ 0.05 considered statistically significant.

Ethical consideration

The approval to undertake the study was sought and obtained from the Ethics Review Committee of the University of Port Harcourt, Port Harcourt, while informed consent was sought and obtained from the management of the University of Port Harcourt Teaching Hospital and the heads of all the study sites.


  Results Top


A total of 36 air quality measurements were carried out in nine study sites in the hospital. The wind speed in the study sites ranged from 0.07 m/s in the Anatomical Pathology Laboratory (APL) and the antenatal clinic to 0.27 m/s in the urology clinic, with a mean of 0.13 m/s. There were detectable bacteria and fungi in the ambient air of all the study sites. The mean bacteria count of the ambient air of the study sites are presented in [Table 1]. The mean bacterial count ranged from 9.5 CFU/m 3 in the urology ward to 199.33 in the HIV clinic, with a mean of 80.0 CFU/m 3 for the nine study sites.
Table 1: The mean bacteria count of the ambient air of the study sites

Click here to view


The bacteria cultured from the study sites include Staphylococcus (25.10%), Streptococcus (20.28%), Bacillus cereus (21.73%), Klebsiella (8.98%), and Escherichia coli (18.36%). Staphylococcus (36.36%) and Streptococcus (27.27%) were the most frequent bacteria isolated in the surgery outpatient clinic (SOC); Klebsiella (15.79%) was the most predominant in the immunization clinic; E. coli (28.57%) were the most common in the APL, while B. cereus (36.36%) was most frequently isolated in the gynecology ward.

The bacteria count during and after the peak working hours are presented in [Table 2]. The bacterial count increased at the end of the working day in all the wards and clinics, except at the antenatal clinic where the count decreased from 227.33 CFU/m 3 when the clinic was in session to 49.00 CFU/m 3 , an hour after the last patient was seen. On the other hand, the bacterial counts were highest in the laboratories during the peak working hour, with a mean count of 105.67 CFU/m 3 recorded at the microbiology laboratory during the peak working hours compared to 62.33 CFU/m 3 at the close of work.
Table 2: The bacteria count of the study sites during and after the peak working hours

Click here to view


The mean fungi count of the ambient air of the study sites is presented in [Table 1]. The mean fungi count ranged from 10.5 CFU/m 3 in the SOC to 23.5 in the APL, with a mean of 16.9 CFU/m 3 for all the study sites. The fungi cultured from the study sites include Aspergillus species (20.30%), Penicillium species (23.54%), Fusarium (2.50%), Trichophyton (5.21%), Candida species (25.37%), and Rhizopus (23.04%). Aspergillus species (37.48%) had the highest count in the HIV clinic, Penicillium species (38.46%) were the highest in the SOC, Fusarium (8.11%) was highest in the HIV clinic, Trichophyton (13.85%) was highest in the immunization clinic, Candida (43.75%) was highest in the antenatal clinic, while Rhizopus (34.78%) was predominant in the gynecology ward. The fungal count during and after the peak working hours are presented in [Table 3]. The fungal count increased in all the study sites at the end of the working day.
Table 3: The fungi count of the study sites during and after the peak working hours

Click here to view



  Discussion Top


The study showed the presence of different species of bacteria and fungi in the ambient air of all the study sites. This is consistent with the findings of the other studies carried out in Nigeria [13],[14] and the developed countries. [15] The types and number of airborne bacteria and fungi in the study sites seem to be influenced by the type of activities carried out in the study site; the type and number of patients at the site, the level of ventilation, and the level of hygiene of the study site.

The type of activities carried out is likely to be responsible for the high levels of airborne bacteria recorded in the laboratories during the peak working time. This is because laboratory services, especially those carried out in the microbiology and the anatomical pathology laboratories, in countries where communicable diseases are still very prevalent often results in the generation of airborne microorganisms. [17]

The type and number of patients at the study sites possibly explain the high bacteria and fungi counts recorded at the HIV clinic and the antenatal clinic. HIV patients are known to also suffer from several other communicable diseases; [18] they also have an overgrowth of the normal body flora, both of which can be discharged into the air, especially with the level of immune-depression suffered by many of the HIV patients. The high prevalence of candidiasis among pregnant women [19] is also likely to be responsible for the very high level of Candida species recorded in the ambient air of the antenatal clinic.

There is a direct relationship between ventilation and indoor levels of bacteria and fungi, with high ventilation associated with lower levels. [11] The wind speed in the APL and the antenatal clinic was just 0.07 m/s, which is obviously not enough to achieve the recommended minimum of 60 L/s/patient for general wards and outpatient departments, needed to reduce the levels of airborne microorganisms in the ambient air. [11] The poor ventilation at the laboratory and clinic is therefore an important explanation for the high level of bacteria and fungi in these study sites.

The hygiene practices at the study sites can be the explanation for the decrease in the bacteria count recorded in the laboratories at the end of the working day, and for the increase in the fungi count recorded in all the study sites, after the peak working period. Most of the specimens handled in the laboratories of the study hospital contained microorganisms that could have been sent airborne in the course of working on the specimens, especially with the little containment measures used in the laboratories. [17] The airborne microorganisms accumulate in the laboratory in the course of the working day but decreases, especially with the thorough cleaning that takes place at the end of the working day. The fungi count in all the study sites however remained high after the working day, possibly because some of the cleaning agents used in the hospital are not effective against fungi, [20] which therefore continue to build up until they are slowly dispersed by air flow. The fact that fungi commonly grow in various areas of the hospital environment and can be dispersed in the course of work [17],[21] is also a possible explanation for the build-up of fungi at the end of the working day in all the study sites.

The bacteria and fungi cultured from the study sites are the same as the ones cultured in the other Nigerian studies. [13],[14] The cultured bacteria are mostly pathogenic and have been implicated in many nosocomial infections. Staphylococcus species and Streptococcus species formed 25.1% and 21.27% of all the bacteria cultured from the study sites but are also associated with a large proportion of surgical site infections. [22] Klebsiella species are the most common bacteria cultured from the immunization clinic, but the bacteria is also able to cause urinary tract infection and bacteremia in the under-five children that receive the childhood immunization at the clinic. [23] B. cereus was found in all the study sites, especially in the gynecology ward where it is able to exacerbate nausea and vomiting that are common in pregnant women, apart from other gastrointestinal symptoms. [24]

Mycobacteria tuberculosis was not cultured from the study sites, especially in the HIV clinic. This is not likely to be due to the absence of the bacteria in the study sites, considering the prevalence of active tuberculosis among HIV-positive patients. It is however more likely to be due to the fact that the M. tuberculosis is very difficult to culture, and almost impossible to culture with the sedimentation method we used for the study. [25] Airborne M. tuberculosis in hospitals have been shown to be very infectious, such that health workers in endemic countries ultimately become infected in course of their working life. [10]

Fungi were detected in the ambient air of all the study sites; their medical importance is not only in their roles in nosocomial infections [26] but also in their actions as allergens and toxins. [27] Fungi such as the Penicillium species, Rhizopus, and Aspergillus species cultured from all the study sites are prolific sources of allergens that can trigger off the asthmatic attack and other allergic reactions. [27]

The health hazards posed by the type and count of the bacteria and fungi in the ambient air of the study sites call for corrective actions. Whereas little ethical actions can be taken to reduce the source of the microorganisms in patients, there are however many corrective actions that can be applied to reduce the ambient levels of the bacteria and fungi. These actions include increasing the ventilation in the study sites to a minimum of 60 L/s/patient and improving the hygiene levels in the study sites, especially in sites such as the HIV clinic with high counts of bacteria and fungi in their ambient air, with vulnerable patients that can be infected. These corrective actions are not one-off but require sustained and coordinated efforts that are better delivered by a deliberate Indoor Air Quality Management Programme. This program should be headed by an engineer in the works department of the hospital, but with useful inputs from the environmental health department. [28]

A major limitation of our study is the inability of the culture media used for the study to effectively culture some microorganisms such as M. tuberculosis that are of great clinical significance.


  Conclusion Top


The number and types of bacteria and fungi cultured from all the study sites have the potential to cause ill health. Corrective actions are therefore needed to keep the microorganisms within regulatory levels by improving ventilation and hygiene, especially in at-risk sites.

Financial support and sponsorship

Nil.

Conflicts of interest

There are no conflicts of interest.

 
  References Top

1.
Murray CJ, Lopez AD. The global burden of disease: A comprehensive assessment of mortality and disability from disease, injuries and risk factors in 1990 and projected to 2020. Boston, MA: Harvard University Press, 1996.  Back to cited text no. 1
    
2.
Wyatt HV. The popularity of injections in the Third World: Origins and consequences for poliomyelitis. Soc Sci Med 1984;19:911-5.  Back to cited text no. 2
[PUBMED]    
3.
World Health Organization. Current and future long-term care needs. Geneva: World Health Organization, 2002.  Back to cited text no. 3
    
4.
Ikeda RM, Birkhead GS, DiFerdinando GT Jr., Bornstein DL, Dooley SW, Kubica GP, et al. Nosocomial tuberculosis: An outbreak of a strain resistant to seven drugs. Infect Control Hosp Epidemiol 1995;16:152-9.  Back to cited text no. 4
    
5.
Johnston CP, Qiu H, Ticehurst JR, Dickson C, Rosenbaum P, Lawson P, et al. Outbreak management and implications of a nosocomial norovirus outbreak. Clin Infect Dis 2007;45:534-40.  Back to cited text no. 5
[PUBMED]    
6.
Muyembe-Tamfum JJ, Kipasa M, Kiyungu C, Colebunders R. Ebola outbreak in Kikwit, Democratic Republic of the Congo: Discovery and control measures. J Infect Dis 1999;179 Suppl 1:S259-62.  Back to cited text no. 6
[PUBMED]    
7.
WHO. Health through safe health care: Safe water, basic sanitation and waste management in health care settings. Geneva: World Health Organization, 2005.  Back to cited text no. 7
    
8.
Struelens MJ. The epidemiology of antimicrobial resistance in hospital acquired infections: Problems and possible solutions. BMJ 1998;317:652-4.  Back to cited text no. 8
[PUBMED]    
9.
Adams J, Bartram J, Chartier Y, editors. Essential Environmental Health Standards in Health Care. Geneva: World Health Organization, 2008.  Back to cited text no. 9
    
10.
Menzies D, Fanning A, Yuan L, FitzGerald JM. Hospital ventilation and risk for tuberculous infection in Canadian health care workers. Canadian Collaborative Group in Nosocomial Transmission of TB. Ann Intern Med 2000;133:779-89.  Back to cited text no. 10
[PUBMED]    
11.
Atkinson J, Chartier Y, Pessoa-Silva CL, Jensen P, Li Y, Seto WH, editors. Natural Ventilation for Infection Control in Health-care Settings. Geneva: WHO, 2009.  Back to cited text no. 11
    
12.
Ordinioha B, Sawyer W. The environmental health condition of the new University of Port Harcourt Teaching Hospital. Niger Health J 2012;11:117-9.  Back to cited text no. 12
    
13.
Agbagwa OE, Onyemaechi SA. Microbiological quality of indoor air of a general hospital and a health center in Rivers State Nigeria. Int J Curr Microbiol Appl Sci 2014;3:424-31.  Back to cited text no. 13
    
14.
Omoigberale MN, Amengialue OO, Iyamu MI. Microbiological assessment of hospital indoor air quality in Ekpoma, Edo State, Nigeria. Glob Res J Microbiol 2014;4:1-5.  Back to cited text no. 14
    
15.
Cabo Verde S, Almeida SM, Matos J, Guerreiro D, Meneses M, Faria T, et al. Microbiological assessment of indoor air quality at different hospital sites. Res Microbiol 2015;166:557-63.  Back to cited text no. 15
    
16.
Barnet HL, Hunter BB. Illustrated Genera: Imperfect Fungi. 4 th ed. New York: Burgress, 1998; 1-218.  Back to cited text no. 16
    
17.
Bennett A, Parks S. Microbial aerosol generation during laboratory accidents and subsequent risk assessment. J Appl Microbiol 2006;100:658-63.  Back to cited text no. 17
[PUBMED]    
18.
Ugochukwu EF. HIV/TB co-infection in Nigerian children. Niger Med J 2010;51:120-4.  Back to cited text no. 18
  Medknow Journal  
19.
Okonkwo NJ, Umeanaeto PU. Prevalence of vaginal candidiasis among pregnant women in Nnewi town of Anambra State, Nigeria. Afr Res Rev 2010;4:539-48.  Back to cited text no. 19
    
20.
Gupta AK, Ahmad I, Summerbell RC. Fungicidal activities of commonly used disinfectants and antifungal pharmaceutical spray preparations against clinical strains of Aspergillus and Candida species. Med Mycol 2002;40:201-8.  Back to cited text no. 20
[PUBMED]    
21.
Herrero B, Zaldivar P. Effects of meteorological factors on the levels of Alternaria and Cladosporium spores in the atmosphere of Palencia, 1990-1992. Grana 1997;36:180-4.  Back to cited text no. 21
    
22.
Cantlon CA, Stemper ME, Schwan WR, Hoffman MA, Qutaishat SS. Significant pathogens isolated from surgical site infections at a community hospital in the Midwest. Am J Infect Control 2006;34:526-9.  Back to cited text no. 22
[PUBMED]    
23.
Bonadio WA. Klebsiella pneumoniae bacteremia in children. Fifty-seven cases in 10 years. Am J Dis Child 1989;143:1061-3.  Back to cited text no. 23
[PUBMED]    
24.
Bottone EJ. Bacillus cereus, a volatile human pathogen. Clin Microbiol Rev 2010;23:382-98.  Back to cited text no. 24
[PUBMED]    
25.
Woods GL. The mycobacteriology laboratory and new diagnostic techniques. Infect Dis Clin North Am 2002;16:127-44.  Back to cited text no. 25
[PUBMED]    
26.
Sudharsanam S, Swaminathan S, Ramalingam A, Thangavel G, Annamalai R, Steinberg R, et al. Characterization of indoor bioaerosols from a hospital ward in a tropical setting. Afr Health Sci 2012;12:217-25.  Back to cited text no. 26
[PUBMED]    
27.
Lacey J, Dutkiewicz J. Bioaerosols and occupational lung disease. J Aerosol Sci 1994;25:1371-404.  Back to cited text no. 27
    
28.
Leung M, Chan AH. Control and management of hospital indoor air quality. Med Sci Monit 2006;12:SR17-23.  Back to cited text no. 28
[PUBMED]    



 
 
    Tables

  [Table 1], [Table 2], [Table 3]


This article has been cited by
1 Retrofitting for Improving Indoor Air Quality and Energy Efficiency in the Hospital Building
Chro Hama Radha
Sustainability. 2023; 15(4): 3464
[Pubmed] | [DOI]
2 Indoor air microbial load, antibiotic susceptibility profiles of bacteria, and associated factors in different wards of Arba Minch General Hospital, southern Ethiopia
Gebre Kayta, Aseer Manilal, Dagimawie Tadesse, Munira Siraj, Joseph Selvin
PLOS ONE. 2022; 17(7): e0271022
[Pubmed] | [DOI]
3 Potentially pathogenic bacteria isolated from neglected air and surfaces in hospitals
Mayk Teles de Oliveira, Lorranny Mayara Silva Cunha, Fernanda Cardoso Cruz, Nathany Kelly Ribeiro Batista, Eric de Souza Gil, Virgínia Farias Alves, Maria Teresa Freitas Bara, Ieda Maria Sapateiro Torres
Brazilian Journal of Pharmaceutical Sciences. 2021; 57
[Pubmed] | [DOI]
4 Assessment of Airborne Bacterial and Fungal Communities in Shahrekord Hospitals
Davood Jalili,MohamadHadi Dehghani,Abdolmajid Fadaei,Mahmood Alimohammadi,John Ssempebwa
Journal of Environmental and Public Health. 2021; 2021: 1
[Pubmed] | [DOI]



 

Top
 
 
  Search
 
Similar in PUBMED
   Search Pubmed for
   Search in Google Scholar for
 Related articles
Access Statistics
Email Alert *
Add to My List *
* Registration required (free)

 
  In this article
Abstract
Introduction
Materials and Me...
Results
Discussion
Conclusion
References
Article Tables

 Article Access Statistics
    Viewed6428    
    Printed455    
    Emailed0    
    PDF Downloaded608    
    Comments [Add]    
    Cited by others 4    

Recommend this journal


[TAG2]
[TAG3]
[TAG4]